Modbus to DeviceNet protocol converter
PXB-6022

PXB-6022 is a protocol converter for Modbus to DeviceNet launched by Zhiyuan Electronics. Modbus supports RTU and TCP protocols. It can connect the Modbus device to the DeviceNet master station system, or support Modbus and DeviceNet networks to transmit data seamlessly between PLC control systems.

Features

Small volume at industrial grade;


9V~36V wide voltage supply;


Multiple interfaces:

  • 1-channel standard 10/100M Ethernet;

  • 1-channel isolation CAN;

  • 1-channel isolation RS485;


Modbus to DeviceNet slave station protocol conversion;

  • Support Modbus RTU and TCP master station mode;

  • DeviceNet provides the Baud rates of 125K, 250K and 500K;

  • Support DeviceNet I/O scanning;

  • Support the software to change the DeviceNet address;

  • Provide standard EDS files of DeviceNet;

  • 15 different levels of input and output bytes are for options,Up to 512 bytes input and 512 bytes output.

Diagrams of typical cases

PXB-6022 (connect Modbus devices to AB, Schneider, Omron and other master station devices supporting the DeviceNet network.)

Parameters

Dimension: 84mmx63mmx30mm
Shell material: Metal
Mounting mode: Hangers-mounted
Storage temperature: -40~85℃
Operating temperature: -40~85℃
Power supply: 9~36V
Power consumption: 12V/100mA
Reverse voltage protection: Available
Anti-interference and radiation resistance in industrial environment:  
ESD: Contact: ± 4kV; air: ±8kV 
EFT: Power supply: ±1kV; signal: 0.5 kV
Surge: Power supply: 1.0 kV; signal: 0.5 kV
RF field induction: Power supply: 3 V/m; signal: 3 V/m